You’ll likely need engagement from your fire engineer and Architect but along with them Monkeytoe can provide a stair design service which complies with their requirements, structural requirements and the building code (link to custom design or other design links). The design then flows through manufacture and even installation if required.
This piece will help guide you on your choice of design specification. This guide outlines information in the acceptable solution D1/AS1, for clarification on details please consult this document and relevant AS/NZS standards and literature. All stairs are required to be designed to enable the safe exit of occupants in the event of a fire. To confirm the width, design category, landings, required length/distance and number of people it services requires the building to be assessed by a relevant professional.
STAIR DESIGN CATEGORY
What are the different types of Stairs?
The Design Category of stairs can be defined broadly into two primary and four subcategories:
One: Public Access – See the Monkeytoe Solution here
Two: Service/ Private – See the Monkeytoe Solution here
These classifications govern the pitch or angle, depth of steps and other design characteristics. For example, a ‘Common’ stair can be steeper and have open steps whereas an ‘Accessible’ stair must have a closed design and a wider tread. If the stairs are the only access in a publicly accessible building at least one set must be a ‘accessible’ stair and the second may be a common, service, or private stair depending on the site specifics. Accessible stairs are not required for private dwellings and small industrial buildings.
Accessible Stairs
These are the easiest access stairs with the gentlest pitch with handrails both sides and are designed to be able to be used by those with impaired mobility if needed. These are typically for public facilities main access, and larger commercial building access stairs. Some buildings can have one accessible route and often a second stair can be classified as a common, service or private stair depending on the fire evacuation design.
Common Stairs
These are most common stairs and for multistorey applications as well as external stairs such as secondary fire escape stairs. These can be accessible to the public but not required to provide for disabled access. Applications include entrance stairs to houses and apartments and externally mounted fire escape stairs. Depending on the fire evacuation design some applications may have multiple Common stairs instead one accessible stair. For the purpose of simplification this includes ‘Main Private’ stairs as defined by D1/AS1.
Private Stairs
These provide private access to a single household unit bedrooms or bathroom areas but not access to kitchens, living rooms garages, does not include external stairs access to verandas and those that are accessible by the public. These are defined by D1/AS1 as ‘Minor Private’ stairs. Secondary Private stairs are not included in this document.
Service Stairs
These are secondary stairs to provide access for service personnel or goods delivery, does not include external stairs access to verandas and those that are accessible by the public. These are defined in D1/AS1 as ‘Service’ stairs
Restricted Access Stairs
Areas that are closed by gates or doors or bars and have access restricted to normal occupants are covered by the standard AS1657-201. These are often incorporated with service and maintenance walkways such as roof top and plant area access systems. These can be steeper and narrower than normal stairs used for everyday use. When specifying these stairs, it is often required to clarify the status of AS1657 as an acceptable solution for this application with the consenting authority.
Stair Design Cheat Sheet
Table 1 is a quick reference showing the limits that stairs need to be designed to according to D1/AS1 and AS1657- 2018, for more information read the descriptions below and the standards themselves.
Stair Design Limits D1/AS1 and AS1657 | ||||
Design Feature | Accessible Stairs | Common Stairs | Service/Private1 Stairs | Restricted Access (AS1657) |
Max Height Per Flight | 2.5m | 2.5m | 4m | 4m |
Max Height before change of Direction4 | 8m | 8m | 8m | 8m |
Pitch Angle | 23⁰ – 32⁰ | 23⁰ – 37⁰ | 23⁰ – 47⁰ | 20⁰ – 45⁰ |
Max Step Height | 180 | 190 | 220 | 225 |
Min Tread Depth | 310 | 280 | 220 | 185 |
Riser Style | Closed | Closed, Open if accessible alternative stair available 1 | Open1 | Open |
No of risers per flight | ≤13 | ≤13 | ≤18 | ≥2 ≤18 |
Width between handrails | 900 mm | 900 mm | 6002, 850 mm3 | 600 mm2 |
Landings | 900 mm | 900 mm | 900 mm | 600 mm |
Handrails | Both sides | One side ≤2 m | One side ≤2 m | One side ≤ 1 m |
Tread Projection | 0-25 mm | 0-25 mm – 15 min for Open | 25 mm – 15 min for Open | ≥-30 mm |
1For more information on Secondary Private stairs see D1/AS1, not covered here.
2For maintenance access systems covered by AS1657-2018, not covered in D1/AS1 for service or private 3Required for multi-unit dwellings and recommended for private, 600 mm is OK for service stairs 4Can also be achieved by landings see change of direction info and D1/AS1 |
Stair Design Features
Stair Widths
How wide should my Stair be?
Stairway width is always measured between handrails, the minimum width for Accessible and Common stairs is 900 mm. For Multi-unit residential stairs, the minimum is 850 mm, this is recommended but not mandatory for private stairs. For service stairs and for normally restricted area access systems for e.g., roof maintenance and building services access the minimum width is 600 mm this is covered by AS1657-2018 rather than D1/AS1. It must be noted that for larger buildings the width of stairs is also governed by the fire escape methodology developed by the fire engineer.
Handrail Requirements
Do I need Handrails? Which Handrails Do I need?
Handrails should always be on both sides for all Accessible stairs, and Common and Private stairs greater than 2m wide. A central handrail is required for widths greater than 4m. For other stair types a single handrail is permitted for widths less than 2m. Handrails are not required for short steps of 2 or 3 risers for common or private residential applications. Handrails should be continuous except for door openings. Areas subject to overcrowding such as cinemas and shopping malls have a requirement for higher design loadings and must be specified as C5 barriers, other stair handrails are C3 (AS/NZS1170.1). When access is used by children under 6yrs all handrail gaps must be no greater than 100mm.
Handrails Location
They must be mounted 900mm – 1000 mm above the landing and stair nosing, it transitions to a height of 1100 mm when on top of a barrier on an intermediate landing. This is because barriers to landings must have total minimum height of 1100 mm high as required by F4/AS1.
Handrails must extend 300mm past the end of the steps for accessible stairs
The handrails must be 45-60 mm from the side of the wall or stair, 90 mm from the top of the handrail to the mounting bracket and a min of 100 mm beneath overhangs.
The handrails are not allowed to intrude into the working area of the stair and landing area except for central handrails including those on the inside of a change of direction landing.
Landings
Landings are the space required at the top and bottom of each flight for resting, access and changing direction. Landings are required on all stairs where the rise is greater than 600 mm. Where a door opens onto the landing a space of 400 mm(600 mm for AS1657) is required to be free of the door edge while opening.
Change of Direction
A change of direction or a landing length of more than 1800 mm (2m for AS1657) is required when consecutive in line stairs rise greater than 8m. The change of direction must be at least 30⁰ (90⁰ for AS1657)
Open & Closed Risers
Do I need Open or Closed Risers?
Open risers are allowable on service and private stairs, when able to be accessed by children 6 years and under the maximum opening must be 100 mm. When there is an accessible alternative available common stair may have open risers. Accessible stairs must always have closed risers.
Tread Projection, Edge Nosing (Stair Nosing Compliance Requirements)
Treads on Accessible and Common stairs which are required to have closed risers have a maximum tread projection of 25 mm. For Common and Service/Private which can have open risers’ stairs must have a minimum projection of 15 mm and a maximum of 25 mm, if closed risers are used a minimum of 0 mm is acceptable. All stairs require the leading edge to be visible, this is normally achieved with a visibly contrasting nosing cover which also provides extra grip. (Lighting can be used in some situations for non-Accessible stair applications)
Fire Escape Stairs
Fire Escape Stairs are designed to provide a means of escape during a fire. They will be categorised as accessible, common or service depending on each application. Depending on the location and function of these they need to be structurally sound and keep the users safe during evacuation. Aluminium is a Lightweight Long-lasting material ideal for fire exit stairs. The design and placement of the stair needs to ensure any fire protection systems are independent of the stair to provide proper protection. This can be achieved by protective shielding, locating stairs in their own fire cell or locating them away from the side of buildings and window openings
Other Requirements
Other requirements that need to be considered but not covered in this document are slip resistance, visibility, obstructions, fire engineering requirements and engineering loads. For more information on these please refer to the relevant standards and MBIE literature.
Stair Terminology
ACCESSIBLE STAIR/STAIRWAY – A stairway having features for use by people with disabilities. Usually required in places that the public use, regardless of whether a lift is provided. Not required for private dwellings and small industrial buildings.
COMMON STAIR/STAIRWAY – A stairway which is used able to be accessed by the public but not required to have features for the disabled. Typically for private dwellings entrance, external stairs, and small industrial buildings. NOTE: a Main Private Stair has the same requirements as a Common Stair
SERVICE STAIR/STAIRWAY- A stairway that is used infrequently by service personnel to gain access to spaces for the service and maintenance of goods.
PRIVATE STAIR/STAIRWAY: A stair used by a household unit.
FLIGHT: The set of steps in between two landings
RISER: The vertical height of the step determined by measuring from the top of each surface
PITCH: The Angle of the stair obtained by measuring the angle from the front edge of each step
OPEN RISER: Stairs having no material on the vertical face between the treads
TREAD DEPTH: The measurement of the tread taken from the front to the back edge for open risers and from the front edge to the back corner for closed risers
TREAD PROJECTION: The amount each step overhangs the one below that
Commercial Stair Code Requirements & Design (Including Common, Private, Service, Accessible & AS1657 Stairs).